Input/Output Circuit Description

2-6

Q1

Active from Figure 2-9

Inhibit from Figure 2-9

Active from Figure 2-9

Voltage to

Primary Control Board

Analog

Current

Output

Converter

50

OHM

From

+25.2V

Current

Current

From

Termination

Panel

Microprocessor

125mA

Voltage to

+25.2V

Converter

Inhibit from Figure 2-9

50

OHM

Microprocessor

125mA

Primary Control Board

Reset

DAC

DAC

Reset

Isolated Discrete Inputs


The T6200-C Controller can be configured for up to 16 isolated discrete inputs. The T6200-D Controller
can be configured for up to 28 isolated discrete inputs in addition to the four internally power discrete
inputs. The resistor, in series with the input, is used to limit the maximum current to less than 6.5
milliamperes. In reference to Figure 2-5, the resistor across the opto-isolator is used to increase the
minimum input current to greater than one milliampere.

The opto-isolator provides electrical isolation between inputs and other circuits. Each input is protected
with fuses. A 100 volt transient absorber is provided on each input terminal to prevent arcing between
conductors on the circuit board. The maximum voltage that can be applied continuously is 38 volts dc or
30 volts ac (rms, sine wave). Discrete input channels 22, 31, and 32 can be used as frequency inputs, with
input frequencies up to 25 kHz. Other discrete inputs can be used as frequency inputs with input
frequencies up to 500 Hz.

Discrete Inputs with Excitation from Controller


The discrete input is similar to the isolated discrete input above, without the isolation. The input is
internally powered. In this configuration a separate internal +24 volt regulator is provided for each dry
contact input. Each voltage regulator has thermal, reverse voltage, and short circuit protection. The
regulator supplies up to five milliamperes.

A contact closure between + and – terminals will activate the input. Refer to Figure 2-6. The internally
powered discrete input represents the standard discrete input jumper selection. The T6200 Controller has
a minimum of four internally powered discrete inputs.

Analog Current
Output