Serial communication connection – Rockwell Automation T6200 Compressor Anti-Surge and Capacity Controller User Manual
Page 50

Hardware Installation/Maintenance
3-28
Serial Communication Connection
The T6200 includes two individual RS-232/RS-485 serial port connections (COMM 1 and COMM 2)
with RJ-45 connectors to facilitate serial communication. COMM 1 and COMM 2 are software
configurable for either RS-232 or RS-485. See Appendix C Modbus Interface RS-232 for COMM
1 and COMM 2 RS-232/RS-485 Configuration. Note: RS-485 is not multidrop. Refer to Figure 3-8,
Figure 3-9, or Figure 3-10 for appropriate COMM 1 and COMM 2 connector location. Note: Non-
Redundant Dual Remote I/O Backplane (Figure 3-10) has only COMM 1 for the Primary and Second
Control Board. Refer to Figure 3-26 for COMM 1 and COMM 2 connector pin assignments.
Pin
Signal
1
NC
2
NC
3
TD (RS-232)/COMM-(RS-485)
4
SG (SIGNAL GND)/COM
5
SG (SIGNAL GND)/COM
6
RD (RS-232)/COMM+ (RS-485)
7
NC
8
NC
Pin 1
Pin 8
FIGURE 3-26
Serial
Communication
Connector