Hardware Installation/Maintenance

3-28

Serial Communication Connection

The T6200 includes two individual RS-232/RS-485 serial port connections (COMM 1 and COMM 2)
with RJ-45 connectors to facilitate serial communication. COMM 1 and COMM 2 are software
configurable for either RS-232 or RS-485. See Appendix C Modbus Interface RS-232 for COMM
1 and COMM 2 RS-232/RS-485 Configuration. Note: RS-485 is not multidrop. Refer to Figure 3-8,
Figure 3-9, or Figure 3-10 for appropriate COMM 1 and COMM 2 connector location. Note: Non-
Redundant Dual Remote I/O Backplane (Figure 3-10) has only COMM 1 for the Primary and Second
Control Board. Refer to Figure 3-26 for COMM 1 and COMM 2 connector pin assignments.

Pin

Signal

1

NC

2

NC

3

TD (RS-232)/COMM-(RS-485)

4

SG (SIGNAL GND)/COM

5

SG (SIGNAL GND)/COM

6

RD (RS-232)/COMM+ (RS-485)

7

NC

8

NC

Pin 1

Pin 8

FIGURE 3-26

Serial
Communication
Connector