Hardware Installation/Maintenance

3-16

Wiring and Jumper Placement for T6200C
Channels 23-26

Two-Wire Transmitter

This wiring and jumper
placement is normally
used with isolated
two-wire transmitters
where the transmitter
power is supplied by the
Controller. Refer to
Figure 2-3.

Factory

Default

4-20 mA

Two-Wire

Transmitter

(Isolated)

+

-

SHLD

24 Vdc
Supply

mA Input

(reference to

common

through resistor)

+

-

T6200C Controller

1

Current Inputs

This wiring and jumper
placement is normally
used with four-wire
current transmitters when
the power is not supplied
by the Controller. Refer
to Figure 2-2.

4-20 mA

Transmitter

+

-

mA Input

(Isolated from

common)

+

-

T6200C Controller

1

Power

Source

Transmitter output

may be referenced

to common

SHLD

Analog Voltage Inputs

This wiring and jumper
placement is used for
voltage input. Refer to
Figure 2-1.

DC Voltage
Transmitter

+

-

+

-

T6200C Controller

1

Power

Source

Transmitter output

may be referenced

to common

DC Voltage Input

(Isolated from

common)

SHLD

Analog Current Outputs

0-20mA (4-20mA)
Analog current outputs.
Refer to Figure 2-4.

4-20 mA or

0-20 mA

Receiver

(Isolated)

+

-

mA Output

+

-

T6200C Controller

1

SHLD

Circuit

Common