Data Structures and Expressions

A-4

Tags assigned by the firmware, their data types, and their descriptions are listed in a
Table A1.

Reserved Tags

Tag

Data

Type

Description

ACTIVE_FLG

Boolean

This controller is controlling the process. It is not a reserve
controller.

BIAS

Real

Bias auxiliary for PID ratio and bias subfunctions.

CD

Real

Derivative gain as calculated so far during this scan. It is

initialized at the start of each scan from the loop auxiliary

CRATE.

CGAIN

Real

Loop proportional gain auxiliary.

CI

Real

Integral gain as calculated so far during this scan. It is

initialized at the start of each scan from the loop auxiliary

CGAIN.

CP

Real

Proportional gain as calculated so far during this scan. It is

initialized at the start of each scan from the loop auxiliary

CGAIN.

CRATE

Real

Loop derivative gain auxiliary.

CRESET

Real

Loop integral gain auxiliary.

DEV

Real

Loop deviation auxiliary.

HOLD-TIME

Real,

Minutes

Length of time the sequence control function is held in

the current batch state.

(FNC #40)

H_FLG

Boolean

Horn flag. This Boolean is set true whenever an alarm

becomes active and is reset to false when the acknowledge

button is pressed. It may also be set to false by the user's

configuration.

LOCAL_ONLY

Boolean

When true, host write-tag commands are rejected unless

"local" is true (in the command). Note: the host must have

"local" on to turn LOCAL_ONLY off. This tag may be

controlled by the LOI to prevent inadvertent updates by the

central operator.

MANUAL-RESET

Real

Manual reset as calculated so far during this scan. It is