Table 9-1, Characteristics performance – Rockwell Automation T6200 Compressor Anti-Surge and Capacity Controller User Manual

Page 172

Advertising
background image

Specifications












Table

9-1

T6200 Controller Electrical Characteristics (T6200”C” module)

Characteristics

Performance

Analog-To-Digital Conversion

Accuracy

Non-Linearity

Resolution

Noise

T6200C only

± 0.2% of full scale

± 0.05% of full scale

12-bits + sign

± 0.1% of full scale

Programmable Gain Amplifier

Gain

Settings

Accuracy G=1/2/4/8/16

T6200C only

1, 2, 4, 8 and 16

± 0.05% / ± 0.05% / ± 0.10% / ± 0.15% / ± 0.15%

Analog Inputs

Number of Inputs:


Signal

Types:Voltage


Current


Common Mode Rejection

Common Mode Protection


Input Res.:Voltage Mode

Current Mode

T6200C only

Up to 20

± 625 mVdc, ± 1.2 Vdc, ± 2.5 Vdc, ± 5 Vdc, and ± 10 Vdc, auto ranging
± 2.5 mAdc, ± 5 mAdc, ± 10 mAdc, and ± 20 mAdc, auto-ranging

80 dB @ 60 Hz (When configured as an isolated input)
100 V transient absorbers

800 k

Ω differential and 400 kΩ common mode

250

Ω +0/-0.04% differential and 400 kΩ common mode

When configured as an isolated input

Analog Outputs


Number of Outputs:

Signal

Type

Output

Load

Resolution
Accuracy
Non-Linearity

T6200C only

4 to 8
0-20 (4-20) mAdc, current sourcing
0-350

Ω; Larger resistance may be used, (see I/O Circuit Description)

12 bits
± 150

µ

A

± 10

µ

A

Discrete Inputs (On/Off)