T6200 – pid fb & variables – Rockwell Automation T6200 Compressor Anti-Surge and Capacity Controller User Manual

Page 150

Advertising
background image

Configuration

8-30

T6200 – PID FB & Variables

-

Loop Variable Editing

: On the FBD configurator Main Window press the

button to

call up the Variable Editor.

Loop Parameter Adaptation: Verify the loop parameters to make sure that they meet the

requirements of your application.


Check the following…
-

PID Tuning Constants, CGAIN, CRESET, CRATE: Enter proper settings for each loop

-

Loop Scan Time, PERIOD: Except for special requirements (AS_PID), select 0.30 seconds

-

Loop Scan Priority, PRIORITY: Except for special requirements, leave default setting

-

Ratio Value of PID block, Ratio: Except for Ratio requirements, select 0

-

Bias Value of PID block, Bias: Except for Bias requirements, select 0

-

Loop Span Limits, SPANLO and SPANHI: Enter desired Span limits for each loop

-

Setpoint Limits, SPHILM and SPLOLM: Enter desired settings for each loop

-

Setpoint Rate Limit, SP_RATE: Enter desired settings for each loop



FIGURE 8-18


Loop Variables