Dimensions and ratings, Gv90, Boiler manual – Weil-McLain GV90+ User Manual

Page 103

Advertising
background image

Part number 550-142-054/0411

103

GV90+

gas

-

fired

water

boiler

— Boiler Manual

Figure 111

Engineering data — see page 101 for additional technical information

Boiler
Model

Water flow rate per boiler

Vent/air pipe size —

Provide a separate vent

for each boiler

Note 1

GPM @ 20°F rise

GPM @ 40°F rise

GV90+3

6.5

3.3

3”

GV90+4

9.7

4.9

3”

GV90+5

13.0

6.5

3”

GV90+6

16.1

8.1

3”

Note 1

All GV90+ installations require a separate vent pipe and termination for each boiler.

Vent piping cannot be manifolded

.

Install and terminate vents as described in vent/air installation instructions in this manual.
Combustion air piping can be individually piped or manifolded. See Figure 37, page 31, for manifolded air piping.

Dimensions and ratings

(continued)