Troubleshooting, Gv90, Boiler manual – Weil-McLain GV90+ User Manual

Page 83

Advertising
background image

Part number 550-142-054/0411

83

GV90+

gas

-

fired

water

boiler

— Boiler Manual

Troubleshooting

(continued)

CHART 3

LIMIT & POWER lights flashing

Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow

instructions could result in severe personal injury, death or substantial property damage.

• This is a

LOCKOUT condition. The return water temperature

sensor has signaled a temperature higher than 240 °F, but the

boiler limit circuit is closed (indicating that the limit control circuit

did not catch the over-temperature condition). This is probably

an indication of a failure of the boiler limit control and possibly

the block temperature switch as well.

TURN OFF POWER to boiler at 120 VAC service switch.

• Remove

CONTROL CIRCUIT plug from IBC receptacle (Fig-

ure 93, page 78, Item 5).

• Remove a wire from one of the limit control spade connec-

tors.

• Connect an ohmmeter across the left and right pins on the

center row of the limit circuit harness.

Does the ohmmeter indicate a shorted wire harness (zero ohms)?

Yes

No

• Replace control wiring harness.
• Retest.

• Replace water temp sensor.
• Retest.

• Close the external manual gas valve.
• Remove one wire from the limit control space

connector.

• Set a thermostat to call for heat. Then turn on

power to the boiler at the 120 VAC service switch.

• The boiler system circulator should come on and

the IBC should try to cycle the boiler.

• Allow the boiler circulator to run to cool off boiler

and system water.

• After the boiler and system water have cooled,

turn off power at the 120 VAC service switch and

open the external manual gas valve.

• Replace IBC.
• Retest.

• Replace limit control and

block temperature switch.

• Retest.

• Reconnect

CONTROL CIRCUIT plug to IBC.

• Remove

WATER TEMP SENSOR plug from IBC receptacle

(Figure 93, page 78, Item 6).

• Connect an ohmmeter across the plug pins to check the sen-

sor resistance.

Does the ohmmeter indicate a shorted sensor (zero ohms)?

Yes

No

• Set limit control knob to its minimum setting. Replace wire to

limit control spade connector.

• Set a thermostat to call for heat.
• Turn on power at 120 VAC service switch.
• IBC should cycle boiler on and begin heating.
• The limit control should shut off the gas valve when the

temperature at the boiler pressure/temperature gauge has

reached no more than about 20 °F higher than the limit

switch setting.

Does limit control shut off gas correctly?

Yes

No

Is boiler hot?

Yes

No