Start-up, Gv90, Boiler manual – Weil-McLain GV90+ User Manual

Page 63

Advertising
background image

Part number 550-142-054/0411

63

GV90+

gas

-

fired

water

boiler

— Boiler Manual

Figure 73

Tools required for gas valve outlet

pressure measurement

1 U-tube manometer with tubing -

Manometer provides a fine scale by
slanting the manometer (Dwyer Model
1227 recommended).

2 Tee hose fitting (provided in high

altitude kit).

3

1

/

16

" flat head screw-

driver.

4 T-40 star drive for

gas valve pressure
regulator cover
screw.

Figure 74

Carefully connect manometer to gas valve

as shown, following instructions on this

page (see legend at left)

5. Position and zero manometer per manufacturer’s instructions. The

manometer must have at least 6” of tubing above the fluid level or

fluid may be drawn into the gas valve.

If manometer fluid is drawn into gas valve body, gas valve

must be replaced. Fluid in valve will cause it to malfunc-

tion, possibly resulting in severe personal injury, death

or substantial property damage.

6. Disconnect tube from hose barb on gas valve vent tap. Connect

tube end to tee hose fitting as shown in Figure 74. Then add length

of hose from tee hose fitting to gas valve vent tap.

7. Connect positive side manometer hose to top of the tee hose fit-

ting (Figure 74).

8. Connect negative side manometer hose to the barrel of the gas

valve outlet pressure tap (Figure 74).

Check gas valve setpoint

1. Open manual gas valve and turn on electrical power to boiler.

2. Start boiler and allow boiler to run for 5 minutes.

3. Read manometer. This is the gas valve outlet pressure set point. If

set point is between – 0.1” w.c. and – 0.3” w.c. go to step 7.

4. If gas valve setpoint is not between – 0.1” w.c. and – 0.3” w.c., use

T-40 driver to remove cap on gas valve pressure regulator.

5. Turn gas valve pressure regulator screw counter clockwise to

lower gas valve set point to – 0.2” w.c.

6. Reinstall cap on gas valve pressure regulator using T-40 driver.

7. Cycle boiler off and on several times to verify gas valve set point.

If set point does not remain between - 0.1” w.c. and – 0.3” w.c.,

readjust as necessary.

8. Close manual gas supply valve and turn off electrical power to

boiler.

9. Remove manometer hose from gas valve outlet pressure tap barrel

and replace sealing screw.

10. Remove tee hose fitting and added tube.

11. Reinstall hose on gas valve vent tap hose barb.

12. Open manual gas supply valve and turn on electrical power to

boiler.

Legend for Figure 74

1 Gas control outlet pressure tap — located on back side of gas control. Use tap

closest to gas control gas outlet —Remove screw from gas control outlet pressure
tap and slide hose over tap

2 Add tee hose fitting as shown
3 Existing hose to gas control vent tap hose barb — Remove from gas control vent

tap and connect to end of tee as shown

4 Gas control pressure regulator cap
5 Honeywell Type VK8115V gas valve
6 Gas outlet vent tap
7 Gas outlet piping
8 Add hose from gas control vent tap to tee hose fitting

Start-up

(continued)