Figure 20

Radiator system — zone-valve zoning

Figure 21

Radiator system — circulator zoning

Radiator system piping

Apply Figure 20 (zone-valve zoning) or Figure 21 (circulator zoning)

to systems using standing cast iron radiators. This applies to gravity

water systems and converted steam systems using columnar, tubular

or recessed cast iron radiators.
The suggested piping for zone-valve zoning radiator systems differs

from baseboard systems because of the high water content of cast iron

radiators. The GV90+ internal circulators automatically regulate supply

and internal bypass flow based on the temperature of the water return-

ing to the boiler. At the start of many heating cycles in a radiator system,

the water in the radiators is cool. So the boiler would slow down system

flow rate while sending out relatively hot water. This could cause heat

distribution problems. Install a separate system circulator as shown

in Figure 20 when zoning with zone valves. The separate circulator

assures a relatively constant temperature drop through the system.
The boiler internal circulators must be left in the boiler. They cannot

be removed for use a zoning circulator. Provide a circulator for each

zone when circulator zoning, and pipe the system as in Figure 21.

Balancing, when required

Substitute a memory-stop

valve for one of the isolation valves in each zone to use

the memory-stop valve for balancing flow as well as

isolation.

Zoning with zone valves

Provide a separate 24-volt

transformer to power the zone valves. Size the trans-

former to handle the total rated load of all connected zone

valves. Alternatively, use a zone valve zone controller.

Zoning with circulators

— The GV90+ internal system

circulator cannot be removed from the boiler for use as

one of the zone circulators. It must remain as shipped

from the factory to allow proper flow control inside the

boiler. You will need a circulator for each zone. Provide

circulator relays or circulator zone controller.

The system circulator must be supplied by the in-

staller.

MINIMUM

Boiler loop pipe size

GV90+3/4
GV90+5/6

1”

1¼”

MINIMUM

Boiler loop pipe size

GV90+3/4
GV90+5/6

1”

1¼”

Legend

1 Isolation valves
2 Automatic air vent (with diaphragm-type expansion tank), or

connect to tank fitting (closed-type expansion tank).

3 Diaphragm- or bladder-type expansion tank, if used. (For closed-

type expansion tank, pipe from top of air separator to tank fitting
as in Figure 15, page 14.)

4 Zone valve
5 System or zone circulator
6 Flow/check valve
7 Hose bibb purge valve
8 Boiler pressure/temperature gauge
9 System supply temperature gauge
10 Differential pressure by-pass valve
16 Cold water fill line — see Figure 15, page 14 for typical components

Install water piping

(continued)