Venting & air — general, Gv90, Boiler manual – Weil-McLain GV90+ User Manual

Page 31

Advertising
background image

Part number 550-142-054/0411

31

GV90+

gas

-

fired

water

boiler

— Boiler Manual

Venting & air — general

(continued)

Figure 37

Combustion air manifold option (combined air inlet, but

individual vents) — must comply with Figure 41, page 35

Figure 38

Maintain clearances and placement between the air

manifold inlet and any appliance vent as shown below

Manifolded combustion air

option for DIRECT VENT

multiple boiler installations

1. Multiple GV90+ boilers can use a common com-

bustion air manifold.
a. The combustion air inlet must be located in a

sidewall (and the

vents must terminate on the

same side of the building

).

b. See below for minimum cross sectional area of

combined air ducts.

c. Provide minimum clearance to adjacent vents

and grade/snow line as shown in Figure 37.

d. Provide minimum free area in duct (adjusted

for louver restriction) of

1 square inch per

2,000 Btuh

total boiler input.

e. If combustion air damper is used, wire to boil-

ers to prevent operation except after damper

has opened.

ONLY air piping can be combined. DO

NOT use combined vent piping. All

vent pipes must be routed and ter-

minated individually as described in

this manual. Flue gas leakage and boiler

component damage can occur. Failure to

comply could result in severe personal

injury, death or substantial property

damage.

Air manifold sizing

1. See Figure 110, page 102 for minimum cross sec-

tional area of combined air ducts.

OR

2. CALCULATE required cross section (for area in

square inches):
a.

MIN. AREA = TOTAL MBH INPUT DIVIDED

BY 2

3. Example:

a. A multiple boiler system with (4)

GV90+5

boilers has a total input of 4 x 140 =

560

MBH

(560,000 Btuh).

b. The required duct cross sectional area is:
c.

MIN. AREA = 560 DIVIDED BY 2

= 280 sq. inches

The air manifold inlet of GV90+ boilers is part of direct vent connections. It is not classified as a forced air intake

with regard to spacing from adjacent boiler vents. To avoid recirculation, however, you must install the vent ter-
minations and air inlets with the clearances specified in Figure 38, page 31. The vent must be located following the
restrictions shown in Figure 41, page 35. The vent termination configuration can be any of the sidewall methods
(NOT VERTICAL) shown in this manual for direct vent or direct exhaust sidewall termination installations.

THE

VENTS MUST BE TERMINATED THROUGH THE SAME SIDE WALL AS THE AIR MANIFOLD INLET

.

Advertising