Start-up, Gv90, Boiler manual – Weil-McLain GV90+ User Manual

Page 65

Advertising
background image

Part number 550-142-054/0411

65

GV90+

gas

-

fired

water

boiler

— Boiler Manual

Figure 75

Integrated boiler control (IBC) sequence of operation — status light indications

STEPS

(After Step 8, the cycle goes back to Step 1)

Call for

Heat?

POWER

TSTAT

CIRC

LIMIT

PRESS

SWITCH

FLAME

Timing

1. Standby

• Waiting for call for heat

NO

2. Call for heat

• Circulator on

YES

3. Limit circuit

• Limit controls closed
• Block switch contacts closed
• Blower on

YES

4. Pressure circuit

• Pressure switch contacts closed
• Ignitor glows

YES

30 sec

5. Flame proven

• Gas valve open
• Ignitor remains on

YES

6 sec

6. Limit cycle

• Limit circuit open
• Gas valve closed
• Blower off after postpurge

YES

30 sec

7. Flame outage *

• Flame out

YES

8. Thermostat satisfied

• Circulator off
• Blower postpurge
• Return to Step 1

NO

30 sec

= ON

= OFF

* If flame is not proven in 4 seconds, boiler recycles 2 times to retry for ignition before going into lockout. Recycle igniter timing

is 30 seconds. Postpurge and prepurge are performed on every cycle. In event of lockout, ignition control will automatically

restore sequence of operation after either:

• 1 hour waiting period.

• Opening and closing of thermostat circuit.

• Removal of 120 VAC power for at least 45 seconds

Start-up

(continued)