Troubleshooting, Gv90, Boiler manual – Weil-McLain GV90+ User Manual

Page 77

Advertising
background image

Part number 550-142-054/0411

77

GV90+

gas

-

fired

water

boiler

— Boiler Manual

c. Immediately disconnect the return temperature sensor plug from

the IBC.

d. Measure the resistance of the sensor. Write down the result.
e. Let the sensor cool to room temperature and measure the resistance

again. Write down the result.

f. Compare the sensor resistances at both temperatures to the closest

temperatures in Figure 91.

g. If the measured values are within 10% of the values listed, the sen-

sor is good. If not, replace the sensor. See Replacement parts for

the part number.

3. Fixed resistor method

a. With the boiler power OFF, disconnect the return temperature

sensor plug at the IBC.

b. Insert a 2500-ohm resistor into the IBC sensor plug.
c. Restart the boiler.
d. If the boiler operates with the resistor, but not with the sensor, try

replacing the sensor. See Replacement parts for the part number.

IBC (integrated boiler control)

Make sure

ground wiring

is installed per wiring diagram. Good grounding

is extremely important for proper operation.

Solder or water

splatter between plugs and circuit board

can cause improper operation of IBC. Place a shield over the

boiler internal controls and components during installation.

Failure to comply could result in severe personal injury, death

or substantial property damage.

IBC indicator lights — lockout modes

• See Charts 1 through 8 in this section for detailed trouble-shooting

procedures.

• To reset control after a lockout, turn off power at the 120 VAC service

switch or turn down all thermostats. Wait 45 seconds. Then restore

power and call for heat.

• After an over-temperature lockout (POWER and LIMIT lights flash-

ing), the control will only reset after interruption of 120 VAC for 45

seconds. (And temperature at return water temperature sensor must

be below 240°F.)

POWER light flashing alone

• Usually indicates reversed polarity of 120 VAC power wires.

POWER and TSTAT CIRC lights flashing

• Usually indicates stray voltage on external thermostat circuit wires

or return water temperature entering boiler sections has not reached

140°F within 20 minutes.

POWER and LIMIT light flashing alternately

• Usually indicates that limit circuit failed to cut off boiler at high tem-

perature — return water temperature sensor has sensed water over

235°F.

POWER and PRESS SWITCH lights flashing

• Usually indicates pressure switch is closed when it should not be, or

pressure switch failed to close within 5 minutes of blower starting.

Troubleshooting

(continued)

Figure 91

Return temperature sensor resistance

Temperature

°F

Resistance

Ohms

Temperature

°F

Resistance

Ohms

60

15300

140

2480

70

11900

160

1680

80

9310

180

1160

100

5840

200

810

120

3760

212

674

Figure 92

GV90+ Integrated Boiler Control (IBC)

POWER and FLAME lights flashing

• Usually indicates control has had three unsuccessful

ignition attempts or sensed flame when it shouldn’t

be there. Boiler may not be properly grounded.

IBC indicator lights —

non-lockout modes

TSTAT CIRC light flashing alone

• Usually indicates return water temperature sensor

detects water at boiler return pipe less than 40°F.

Both internal circulators will run continuously,

even with no call for heat, until temperature rises.

LIMIT light flashing alone

• Usually indicates an open or shorted return water

temperature sensor.

Troubleshooting the IBC

• See Figure 93, page 78 for location of harness plug

receptacles and plugs on the IBC.

Advertising