Troubleshooting, Gv90, Boiler manual – Weil-McLain GV90+ User Manual

Page 81

Advertising
background image

Part number 550-142-054/0411

81

GV90+

gas

-

fired

water

boiler

— Boiler Manual

Troubleshooting

(continued)

Boiler should now operate

normally.

Problem is with incoming

electricity. Have licensed

electrician repair circuit.

Have system checked by a

licensed electrician.
If problem persists, call your

local Weil-McLain sales repre-

sentative.

CHART 1

Troubleshooting POWER light status

Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow

instructions could result in severe personal injury, death or substantial property damage.

TSTAT CIRC

light flashing

CHART 2,

page 82

LIMIT

light flashing

CHART 3,

page 83

PRESS SWITCH

light flashing

CHART 4,

page 84

CHART 6,

page 86

FLAME

light flashing

CHART 5,

page 85

CHART 7,

page 87

NO LIGHT IS

FLASHING,

but there is

insufficient heat

CHART 8,

page 88

Is

POWER light off?

No

Yes

• Make sure service switch or circuit breaker is on or fuses

are good.

• Remove

120 VAC IN plug (Figure 93, page 78, Item 1) on

IBC.

• Using voltmeter, check across top and bottom pins

of

120 VAC IN receptacle.

Does voltmeter indicate

120 VAC?

No

Yes

• Reconnect

120 VAC IN plug.

• Remove

120 VAC transformer PRIMARY plug

(Figure 93, page 78, Item 2) on IBC.

• Using voltmeter, check across top and bottom pins of

PRI-

MARY receptacle.

Does voltmeter indicate

120 VAC?

No

Yes

• Reinstall

120 VAC transformer PRIMARY plug.

• Remove

24 VAC transformer plug (Figure 93, page 78,

Item 7) on IBC.

• Using voltmeter, check across pins of receptacle.

Does voltmeter indicate

24 VAC?

No

Yes

Replace transformer.

Retest.

Replace IBC.
Retest.

Replace IBC.

Retest

Is

POWER light . . .

Flashing

alone?

Flashing with

another light?

On steady

(NOT flashing)?

• Usually indicates polarity on incoming

120 VAC power

line is wrong.

TURN OFF POWER at service switch or breaker, then

reverse the HOT and NEUTRAL wires entering the boiler

in the J-box.

• Restore

POWER at service switch or breaker.

Is

POWER light flashing now?

No

Yes