Troubleshooting, Gv90, Boiler manual – Weil-McLain GV90+ User Manual

Page 82

Advertising
background image

Part number 550-142-054/0411

GV90+

gas

-

fired

water

boiler

— Boiler Manual

82

Troubleshooting

(continued)

CHART 2

TSTAT CIRC & POWER lights flashing

Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow

instructions could result in severe personal injury, death or substantial property damage.

Is return water temperature sensor clamped

securely to the return pipe in the boiler?

Yes

No

• Remove

CIRCULATORS plug (Figure 93, page 78, Item 4)

from plug receptacle of IBC.

• Place voltmeter leads across the right-side

120 VAC N and

120 VAC H pins of the CIRCULATORS receptacle.

Does the voltmeter indicate 120 VAC?

No

Yes

Is boiler internal Bypass circulator operating?

No

Yes

• Test wire continuity of

circulator wire harness.

Is harness ok?

No

Yes

• Check the boiler internal return pipe where it enters the

boiler sections. The

TSTAT CIRC and POWER lights

will flash as long as the return water temperature is less

than 130 °F.

• Wait up to 20 minutes to give the boiler and system a

chance to respond.

Does problem persist?

No

Yes

• Attach sensor to pipe with clamp provided.
• Follow return temperature sensor checking procedure

on page 76. Replace sensor if necessary.

• Retest.

• Check for stray voltage on the incoming thermostat wires.

Disconnect the two external wires connected to the boiler

thermostat wires.

• Connect a voltmeter across the two incoming wires. Close each

thermostat, zone valve and relay in the external circuit one at a

time and check the voltmeter reading across the wires. There

should NEVER be a voltage reading. If a voltage does occur

under any condition, check and correct the external wiring. (This

is a common problem when using 3-wire zone valves.)

• Once the external thermostat circuit wiring is checked and

corrected if necessary, reconnect the external thermostat

circuit wires to the boiler thermostat wires and allow the boiler

to cycle.

Did you find and correct a voltage across the two external thermostat circuit wires?

Yes

No

• Boiler should now operate per the normal sequence of op-

eration (Figure 75, page 65) if wiring was corrected.

• Replace IBC (IBC).
• Retest.

• Boiler may now be operating normal-

ly. Verify against normal sequence of

operation (Figure 75, page 65).

• If boiler appears not to be heating, troubleshoot boiler

per

CHART 8, page 88. If problem cannot be resolved,

replace water temperature sensor and retest. Then re-

place IBC (IBC) if sensor does not correct the problem.

• If boiler is heating, but the temperature at the return

pipe does not increase above 130 °F, there may be an

incorrectly-piped external circulator forcing water through

the boiler. Check external piping and correct.

• Reconnect circulator harness to IBC.
• Attempt to get the circulator started by giving it a sharp rap

on the end of the circulator motor (to release a possibly

locked impeller).

• If the circulator begins to operate, allow it to operate for a

few minutes to see if the problem clears.

• If problem persists, replace the Bypass circulator.
• Retest.

• Replace circulator harness.
• Retest.

Advertising