Troubleshooting, Gv90, Boiler manual – Weil-McLain GV90+ User Manual

Page 85

Advertising
background image

Part number 550-142-054/0411

85

GV90+

gas

-

fired

water

boiler

— Boiler Manual

Troubleshooting

(continued)

CHART 5

FLAME & POWER lights flashing

Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow

instructions could result in severe personal injury, death or substantial property damage.

• Open manual gas valve.`
• Restart boiler, following Operating instructions on boiler

(see Figure 76, page 66).

• Check for proper operation (per normal sequence of

operation).

• Boiler should now operate normally.
• Original flashing

FLAME light caused by igniter not

operating properly.

• See normal sequence of operation (Figure 75, page 65).

• Boiler should now operate normally.
• Original flashing

FLAME light caused by gas valve not

operating properly.

• See normal sequence of operation (Figure 75, page 65).

• Replace IBC.
• Retest.

• Call your local Weil-McLain

sales representative.

Are manual main shutoff valve and gas valve turned on?

No

Yes

• Check gas valve harness wires and check for tight wiring connec-

tions on gas valve and IBC. Repair/replace as necessary.

• Recycle boiler by thermostat or service switch (holding power off for

at least 45 seconds).

• Thermostat should call for heat and appropriate zone valves close.

During step 5 of normal sequence of operation (Figure 75, page 65),

is there

24 VAC across gas valve terminals?

No

Yes

• Check and/or replace igniter.
• Recycle boiler by thermostat or service switch. Thermostat should

call for heat and appropriate zone valves close.

• Wait 5 minutes.

Are

FLAME & POWER lights flashing?

No

Yes

• Check and/or replace gas valve.
• Recycle boiler by thermostat or service switch. Thermostat should

call for heat and appropriate zone valves close.

• Wait 5 minutes.

Are

FLAME & POWER lights flashing?

No

Yes