Venting & air — general, Gv90, Boiler manual – Weil-McLain GV90+ User Manual

Page 32: Gv90+ model maximum vent and air pipe lengths

Advertising
background image

Part number 550-142-054/0411

GV90+

gas

-

fired

water

boiler

— Boiler Manual

32

Venting & air — general

(cont.)

Figure 39

GV90+ venting and air piping — OPTIONS and PIPING LIMITS

Vent length affects boiler input — the boiler automatically derates to compensate for pressure loss through the vent.

See the derate values given in Figure 109, page 101. The longer the vent, the more the input is reduced.

GV90+ Model

Maximum vent and air pipe lengths

(Minimum length for all applications is 2 feet)

(All applications include allowance for the termination fittings)

DIRECT VENT

(combustion air piped to boiler from outside)

DIRECT EXHAUST

(combustion air from inside)

SIDEWALL

termination

VERTICAL

termination

SIDEWALL

termination

VERTICAL

termination

Weil-McLain

vent/air cap

3” PVC

Separate pipes

3” PVC

Concentric

[Note 1]

3” PVC

Separate pipes

3” PVC

Concentric

[Note 1]

3” PVC

Coupling or

W-M Cap

3” PVC

Coupling

See page 37

See page 39

See page 41

See page 43

See page 45

See page 51

See page 53

Max.

Length

(feet)

Max.

Length

(feet)

Max.

Length

(feet)

Max.

Length

(feet)

Max.

Length

(feet)

Max.

Length

(feet)

Max.

Length

(feet)

-3

100

100

100

100

100

100

100

-4

100

100

100

100

100

100

100

-5

100

100

100

100

100

100

100

-6

100

100

100

100

100

100

100

Equivalent feet for elbows — deduct from maximum equivalent length of piping (does not apply to termination fittings)

• 7 feet per for each 3-inch 90° long-radius or 45° elbow
• 16 feet for each 3-inch short-radius elbow

Note 1:

Use only PVC pipe DO NOT use CPVC or ABS with concentric termination kits.

IPEX 3” PVC concentric vent kits can be used with standard PVC pipe, fittings and cement (ANSI/ASTM D1785) except where ULC
S636 compliance is required. For ULC S636 compliance, all pipe, fittings and cement must be IPEX System 636. When using IPEX
kits, use only IPEX product code 196006 for 3” venting.

Contact Weil-McLain for ordering information and availability of Weil-McLain venting kits.