Service & maintenance, Gv90, Boiler manual – Weil-McLain GV90+ User Manual

Page 73

Advertising
background image

Part number 550-142-054/0411

73

GV90+

gas

-

fired

water

boiler

— Boiler Manual

Service & maintenance

(continued)

To clean the burner

The burner may contain ceramic fiber particles. Use

care when handling these materials per instructions on

page 107 of this manual. Failure to comply could result

in severe personal injury.

1. Clean the burner ports with a soft brush.
2. Use compressed air to blow out any particulate if necessary. Use

caution to avoid particulate being blown into the building.

To replace blower assembly

1. Place a new blower flange gasket over the studs at combustion

chamber opening.

2. Reinstall burner cone into chamber opening.
3. Position blower assembly over studs. Install nuts and tighten.
4. Install igniter and new igniter gasket. Fasten with screws and wash-

ers. Tighten only with hand-held screwdriver. DO NOT use electric

or pneumatic driver. Excessive torque will damage igniter. Do not

exceed 20 inch-pounds torque.

5. Connect:

a. Gas valve and piping (4 screws)
b. Gas tubing to gas valve outlet
c. Pressure switch hoses
d. Hose from gas valve to gas/air manifold
e. Air inlet hose
f. Blower motor wiring harness to IBC
g. Igniter harness to igniter plug
h. Blower support bracket (with screw)
i. Ground wire.

6. Be sure all wiring and hose connections are correct per Fig-

ure 81, page 72and are secure on the hose barb fittings.

Inspecting and cleaning the recuperator

Turn off power and gas to the boiler. Failure to do so

can cause severe personal injury, death or substantial

property damage.

Wait several minutes after boiler has stopped to allow

the boiler components to cool to avoid severe personal

injury or death.

1. Remove the recuperator access panel and gasket (see Figure 82)

and inspect the interior with a flashlight.

2. If there are indications of debris or corrosion, disconnect the

condensate trap from the bottom of the recuperator and place a

catch pan underneath.

3. Flush the flueway (Figure 83, item 1) and tubes (Figure 83, item 2)

thoroughly with fresh water, allowing the water to drain out

through the recuperator condensate opening.

4. If all of the water doesn't drain from the flueway (Figure 83,

item 1), the drain holes (see Figure 84) may be plugged. Remove

the recuperator using the procedure under Removing/cleaning/

re-installing the recuperator, page 74.

Figure 82

Recuperator access and cleaning

Figure 83

Recuperator with access panel removed

(GV90+3/4 top, GV90+5/6 bottom)