Install water piping, Gv90, Boiler manual – Weil-McLain GV90+ User Manual

Page 14

Advertising
background image

Part number 550-142-054/0411

GV90+

gas

-

fired

water

boiler

— Boiler Manual

14

Figure 14

Piping to single-zone system using diaphragm- or

bladder-type expansion tank. Boiler connections are

1” NPT (supply from 1” tee, return to 1” recuperator

flange).

Figure 15

Piping closed-type expansion tank

Pipe diaphragm- or bladder-type expansion tanks to the bot-

tom of the separator.

Pipe closed-type (air in contact with water) tanks to the top of

the air separator. Always connect the fill line to the expansion

tank location, as shown above and in the suggested piping.

Install water piping

(continued)

Legend

1

Relief valve discharge piping — see page 12

2

Isolation valves

3

Fill valve

4

Diaphragm-type expansion tank — always locate as

shown in the suggested piping drawings in this manual

5

Air separator

• provide with automatic air vent ONLY when used

with diaphragm-type expansion tanks

• pipe air outlet to expansion tank when used with

close-type tanks

6

Cold fill line, with backflow preventer or check valve

when required by codes (see Figure 15 for typical com-

ponents)

7

System supply piping

8

System return piping

10

Pressure reducing valve, when used

11

Quick-fill bypass valve, when used

12

Closed-type expansion tank — always locate as shown

in the suggested piping drawings in this manual

13

Tank fitting