Troubleshooting, Gv90, Boiler manual – Weil-McLain GV90+ User Manual

Page 75

Advertising
background image

Part number 550-142-054/0411

75

GV90+

gas

-

fired

water

boiler

— Boiler Manual

Troubleshooting

VERIFY PROPER OPERATION AFTER

SERVICING.

Label all wires prior to disconnection when servicing

controls. Wiring errors can cause improper and danger-

ous operation.

Never jumper (bypass) any device except for momentary

testing as outlined in Troubleshooting charts. Severe

personal injury, death or substantial property damage

can result.

The IBC and boiler controls can malfunction if they get

wet. Never try to use a control that has been flooded or

wet. Replace it. Failure to comply can result in severe

personal injury, death or substantial property damage.

The boiler contains ceramic fiber and fiberglass materials.

Use care when handling these materials per instructions

on page 107 of this manual. Failure to comply could

result in severe personal injury.

Before troubleshooting

1. Have a voltmeter that can check 120 VAC, 24 VAC, 24 VDC and

a continuity checker.

2. Check for 120 VAC (min. 102-max.132) to boiler.
3. Make sure thermostat is calling for heat and contacts (including

appropriate zone controls) are closed. Check for 24 VAC between

thermostat wire nuts and ground.

4. Have an inclined manometer with 0 – 2” w.c. range.

Check the following

1. Wire connectors to IBC are securely plugged in at IBC and origi-

nating control.

2. Hoses are properly and securely plugged in and are not dam-

aged.

Checking the air pressure switch

Do not use manometer as shown in Figure 85 to test gas

valve outlet pressure. Where instructed in this manual

to check gas valve outlet pressure, follow instructions

carefully, particularly regarding connection of manom-

eter. Manometer fluid will cause permanent damage to

gas valve. Severe personal injury, death or substantial

property damage can result.

Check switch pressure setting

1. See Figure 85.
2. Remove both air pressure switch hoses from air pressure switch.
3. Install tees and tubing as shown in Figure 85 to inclined manometer.
4. Turn off gas valve and set thermostat to call for heat. Blower will

run but burner will not ignite.

5. Check for 24 VAC between both air pressure switch terminals and

ground.

Figure 85

Connecting a manometer to check

air pressure switch. DO NOT use this

arrangement to check gas valve

6. If manometer reading is at least 1.0” w.c., but there is

not 24 VAC between both air pressure switch terminals

and ground, replace air pressure switch.

Troubleshooting air pressure reading

1. If manometer reading is lower than 1.4” w.c. check for

possible causes:
• Blockage in hoses.
• Loose blower wheel on motor shaft.
• Blower motor not at proper rpm.
• Blockage in air inlet or hose.
• Blockage in flue pipe or termination.
• Condensate trap filled w/condensate.

Return to normal operation

1. When pressure reading is proper and air pressure switch

is operating properly, remove tees and reinstall hoses to
air pressure switch.