Troubleshooting, Gv90, Boiler manual – Weil-McLain GV90+ User Manual

Page 76

Advertising
background image

Part number 550-142-054/0411

GV90+

gas

-

fired

water

boiler

— Boiler Manual

76

Troubleshooting

(continued)

Figure 86

Igniter

Figure 87

Gas valve

Figure 88

Blower housing

Figure 89

Thermal fuse

Figure 90

Return temperature sensor

Igniter

Wait several minutes until igniter cools down before at-

tempting replacement. Failure to do so will cause severe

personal injury.

1. Disconnect igniter (Figure 86) from igniter wiring harness and

remove igniter before removing from blower assembly.

2. Replace igniter gasket if original gasket is frayed or damaged OR

if room-temperature resistance across igniter is not between 40

and 95 ohms.

3. Igniter is fragile — handle with care. Do not touch igniter surface

with bare hands. Body oils can cause failure of the carbide.

Gas Valve

The gas valve (Figure 87) operates with a negative pres-

sure at the outlet — approximately –0.2” w.c. — DO

NOT set gas pressure higher than this.

Follow instructions in this manual carefully if testing

gas valve outlet pressure. Failure to comply can result in

severe personal injury or death.

The gas valve outlet is bolted to the gas line adapter and

sealed with an o-ring. When replacing valve, replace only

with valve listed in this manual for use with the GV90+

boiler. Failure to comply could result in severe personal

injury, death or substantial property damage.

Blower Housing

Do not disassemble blower housing (Figure 88)

. A

fire or explosion causing severe personal injury, death or

substantial property damage can result. If you suspect a

problem, replace blower housing. Follow instructions on

page 72 for blower housing removal and replacement.

Thermal fuse

1. The thermal fuse (Figure 89) protects vent pipe from excess flue

temperatures.

2. If the thermal fuse opens, it must be replaced. See page 94 for

replacement information.

If the thermal fuse opens, investigate the cause before

replacing switch and starting the boiler. DO NOT attempt

to jumper the switch. Failure to comply could result in

severe personal injury, death or substantial property

damage.

Return temperature sensor

1. See Figure 90.
2. Resistance check method:

a. With the boiler operating, use a contact thermometer to

measure the temperature of the return pipe next to the return

temperature sensor. Make a note of the temperature.

b. Turn the boiler ON/OFF switch off.