Multiple boiler water piping

Easy-Fit® piping installation

1. Main header and Easy-Fit

®

Manifold pipe sizing.

a. New system — See page 15.
b. Replacing boilers in an existing system — Without reducing

size, connect system supply and return lines. Install tees or

crosses for Easy-Fit

®

manifolds as shown in Figure 30 or Fig-

ure 31. Size manifolds to handle total connected boiler output

as shown.

2. Provide connections in main header for Easy-Fit® manifolds as

close as possible to the midpoint of multiple boilers.
a. Use tees for four or less boilers, as in Figure 30.
b. Use either tees (Figure 30) or crosses (Figure 31) for five or

more boilers.

3. Manifold placement:

a. To alternate spacing for supply and return lines to boilers,

reverse the short-end and long-end of the manifolds as shown

in Figure 30 and Figure 31.

b. Return manifold must be on the return side of the main and

supply manifold must be on the supply side of the main. Draw-

ings in this manual show flow in system main from right to

left. For system flowing left to right, reverse the locations of

the manifolds accordingly.

4. Connect from Easy-Fit® manifold branches to boiler supply and

return connections using copper or steel pipe, sized for the required

flow rate.

5. Provide a flow/check valve in the supply piping of each boiler as

shown in piping diagrams in this manual. Install an isolation valve

on the supply and return of each boiler as shown. Some local codes

may require the use of individual water level controls and limits

on each boiler when isolation valves are installed.

6. Install main system air eliminator and primary circulator in sup-

ply piping as shown in piping diagrams. Place expansion tank on

suction side of system circulator as shown.

7. Install system accessories as shown in drawings.

8. Piping recommendation drawings:

a. Figure 30 and Figure 31 show details of Easy-Fit

®

manifolds.

b. Figure 32, page 25 is a schematic piping drawing showing the

locations of typical boiler piping and system piping, including

limits and other devices often required by local codes.

c. Figure 33, page 26 and Figure 34, page 27 are three-dimensional

piping drawings of typical multiple boiler installation.

d. Figure 35, page 28 shows recommended piping when an isolat-

ing heat exchanger is needed.

9. If desired, other primary/secondary piping arrangements can be

used.

When using isolation valves on each boiler, some codes

may require providing a low water control and additional

limit for each boiler. Consult local codes to determine

if omission of the individual boiler isolation valves may

allow the use of a single water level control and additional

limit for the entire multiple boiler system.

Maximum connected load per manifold:

2-inch manifold — 450 MBH
3-inch manifold — 1400 MBH
4-inch manifold — 2900 MBH

Figure 30

Single-sided EZ-Fit Header connection

Figure 31

Double-sided EZ-Fit Header connection