Direct vent, Sidewall with 3” concentric, Gv90 – Weil-McLain GV90+ User Manual

Page 42: Boiler manual

Advertising
background image

Part number 550-142-054/0411

GV90+

gas

-

fired

water

boiler

— Boiler Manual

42

DIRECT VENT —

Sidewall with 3” concentric

(continued)

Figure 51

Termination location — concentric

termination — multiple boilers —

clearance from vent of one to air intake of

the next

Figure 52

Installing and supporting the concentric

sidewall vent assembly

Ensure that the wall material is strong

enough to prevent the rain cap from being
pushed inward if struck or pushed from the
outside.

Install termination — concentric pipes

1. Assemble the vent termination as described for concentric termi-

nations, on page 47.

If necessary, you can shorten the lengths of the inner and

outer pipes for a shorter finished assembly. But you must

ensure the pipes butt correctly at both ends. Failure to

properly assemble the concentric termination can result

in flue gas recirculation, causing possible severe personal

injury or death.

2. Wall penetration:

a. Preferably, use a thimble with a 4½-inch hole. If not using a

thimble, carefully use a hole saw to cut a hole not larger than

4¾ inches in diameter through the wall. The finished hole

must provide a solid stop for the rain cap ribs, as shown in the

inset to Figure 52.

3. Secure the termination in place so the rain cap will butt against the

outside wall or outer thimble plate as shown in Figure 52, page 42.

4. Before beginning vent and air piping from the boiler to the con-

centric termination, mount and secure the concentric termination

as shown in Figure 52, page 42.

The vent and air piping must be securely supported, and

must not rest its weight on the boiler fittings. Failure to

properly support the vent and air piping could result in

vent piping damage, resulting in possible severe personal

injury, death or substantial property damage.

The supports/bracing used must support the termination

assembly to prevent slippage or movement.

The clamps used on the outside of the termination pipe

must not cut into the pipe or contain sharp edges that

could cause a crack to form.

When inserting the partially-assembled termination

kit through the wall penetration, wrap plastic or other

protection over the end of the exposed assembly to pre-

vent debris from entering the pipes. If the air passages

become blocked, the boiler will not operate. Once the

rain cap has been cemented to the assembly, there is no

way to correct the problem. The assembly would have

to be replaced if it were cut to be removed and cleaned.

Altering the assembly in any way could result in severe

personal injury or death due to toxic flue product emis-

sions.

When using AL294C stainless vent pipe, use the vent

pipe manufacturer’s PVC adapter when connecting to

the concentric vent attachment.

5. After the assembly has been positioned in the opening and all sup-

ports have been attached, install a bird screen (purchased separately

if not included with the kit) and rain cap as follows:
a. Place the bird screen on the end of the inner pipe as in Fig-

ure 58, page 47.

b. Cement the rain cap in place as shown.

Advertising