Prepare boiler location, Gv90, Boiler manual – Weil-McLain GV90+ User Manual

Page 6

Advertising
background image

Part number 550-142-054/0411

GV90+

gas

-

fired

water

boiler

— Boiler Manual

6

Figure 1

Estimated GV90+ input at altitude

Altitude

(feet)

% Sea level input

1,000

97

2,000

93

3,000

90

4,000

87

5,000

83

5,500

82

6,000

80

7,000

77

8,000

74

9,000

72

10,000

69

Figure 2

Service clearances (recommended)

Prepare boiler location

Installations must follow these codes:

• Local, state, provincial, national codes, laws, regulations and ordinances.
• National Fuel Gas Code, ANSI Z223.1- latest edition.
• Standard for Controls and Safety Devices for Automatically Fired Boil-

ers, ANSI/ASME CSD-1, when required.

• National Electrical Code.
• For Canada only: B149.1 or B149.2 Installation Code and CSA C22.1

Canadian Electrical Code Part 1 and any local codes.

The GV90+ boiler gas manifold and controls met safe lighting and other

performance criteria when boiler underwent tests specified in ANSI Z21.13

— latest edition.

For the Commonwealth of Massachusetts, read and follow

the special instructions located on page 34 of this manual.

Install the boiler so control system components are

protected

from dripping or spraying water or rain

during operation.

Allowing these components to become wet could cause a
boiler failure, resulting in severe personal injury, death or
substantial property damage.

High altitude installations

GV90+ boiler controls automatically reduce input with increasing altitude.

See Figure 1 for estimated input at altitude as a percentage of sea level

input. Multiply the boiler sea level input by this percentage to obtain the

estimated high altitude input. Note that the length of the venting system

will also have a minor impact on input. Refer to the vent supplement for

further information.

No modifications to the boiler should be necessary for installations up to

5,500 feet above sea level. For higher elevations, the air pressure switch

must be changed to a special high altitude switch. Refer to the high altitude

kit instructions, page 10. Note that the gas valve outlet pressure must be

checked (and adjusted if necessary) following instructions on page 62.

DO NOT sidewall vent DIRECT EXHAUST APPLICATIONS

at altitudes above 5,500 feet. Sidewall venting is only allowed

for

DIRECT VENT

applications (ducted combustion air) at

altitudes above 5,500 feet.

Vent length also affects boiler input — the boiler automati-

cally derates to compensate for pressure loss through the vent.

See the derate values given in Figure 109, page 101. For high

altitude installations, multiply the % in Figure 1 times the

value shown in Figure 109 to determine input vs sea level.

Service clearances

When possible, install GV90+ boilers with clearances at least as large as

shown in Figure 2 for best service access.

Flooring

The GV90+ boiler is approved for installation on combustible flooring,
but must never be installed on carpeting.

Do not install boiler on carpeting even if foundation is used.

Fire can result, causing severe personal injury, death or sub-

stantial property damage.

Advertising