Direct vent, Sidewall with w-m vent/air plate, Gv90 – Weil-McLain GV90+ User Manual

Page 38: Boiler manual

Advertising
background image

Part number 550-142-054/0411

GV90+

gas

-

fired

water

boiler

— Boiler Manual

38

Figure 44

Multiple terminations — Weil-McLain vent/

air plate — clearance from vent of one to

air intake of the next

DIRECT VENT —

Sidewall with W-M vent/air plate

(continued)

Figure 45

Hole preparation in wall — Weil-McLain

vent/air plate (use template provided)

1 Inside wall
2 Drill: 3½" diameter for 3" air pipe; locate using template provided
3 For combustible materials, drill: 4" diameter for 3" vent pipe

For noncombustible materials, drill 3½" diameter for 3" vent pipe
Locate opening using template provided

4 Drill mounting screw holes using template provided

Figure 46

Termination assembly — Weil-McLain

vent/air plate

1 Vent termination (3”)
2 Lock washer, #10 (4)
3 Sheet metal screw, #10 x ½” (4)
4 Plastic wall anchor (8)
5 Sheet metal screw, #10 x 1¼” (8)

6 Outer mounting plate
7 Inner mounting plate
8 Vent pipe (butt to screen in termina-

tion)

9 Air pipe (butt to stops in termina-

tion)

Install Weil-McLain vent/air cap

The inside and outside cover plates are stamped to iden-

tify the exhaust (vent) and intake (air) openings. Make

sure to orient the plates correctly.

1. Locate termination opening and avoid obstructions:

a. Use the template supplied with the termination kit.
b. Locate the template on the outside building surface where the

penetration is to be made.

c. Make sure there will be no obstructions that might prevent

proper placement of the termination.

d. Use the template to mark the locations for the four mounting

holes, flue pipe and air pipe. Level the template with a spirit

level.

For the Weil-McLain plate, the template must be level to

ensure the flue and air pipe will be side-to-side, as shown

in Figure 45. Failure to comply could result in severe

personal injury, death or substantial property damage.

e. Cut holes in the wall as shown in Figure 46, using the location

marks made with the template. For best results, use a small-

diameter, long drill bit to drill centering holes for the flue and

air pipe openings. Then drill the large openings from both the

inside and outside.

f. The flue pipe and air pipe may be run through a rectangular

cutout (as marked on the template) in lieu of two separate

holes if desired.

2. Drill holes for the screws or plastic anchors to secure the outside

plate. Install the outside plate and mount the termination on the

plate (temporarily).
a. Cut the flue pipe so the extension through the wall will cause

the vent pipe to fully extend into the termination socket.

b. Cut the air pipe so the extension through the wall will butt the

air pipe against the stops inside the termination.

c. Temporarily slide the flue and air pipes through the opening(s).

Slide the inside wall plate over the two pipes and into position

on the inside wall.

d. Position the inside plate so the flue pipe and air pipe slope

downward slightly toward the boiler (1/4” per foot).

e. Mark the four (4) mounting holes for the plate.
f. Remove the vent and air pipe, drill the four mounting holes,

and mount the inside plate.

3. Test fit the vent/air termination on the vent pipe. Make sure the

vent pipe fully penetrates the termination socket and the air pipe

butts against the interior stops.

4. Apply silicon RTV sealant to the interior of the vent termination

and slide onto vent pipe. Rotate slightly to spread the silicon to

ensure a tight seal around the vent pipe.

5. Secure the termination in place using the four #10 x ½” sheet metal

screws and lock washers (see Figure 46).

Advertising