Annual start-up, Gv90, Boiler manual – Weil-McLain GV90+ User Manual

Page 70

Advertising
background image

Part number 550-142-054/0411

GV90+

gas

-

fired

water

boiler

— Boiler Manual

70

Inspect recuperator

1. Follow the procedure on page 73 to inspect the recuperator and

clean if necessary.

Inspect temperature mixing system

1. Carefully check the

temperature

of the

system return piping

as

it passes through the boiler jacket and on the

return pipe inside

the boiler jacket

just before it enters the boiler sections. You may

do this with a surface pyrometer or by lightly touching the piping

with your fingers.

To avoid potential of severe burn —

Do not rest hands

on or grasp pipes

. Use a light touch only. Return piping

may heat up quickly.

2. The temperature of the water entering the system should quickly

heat up to about

140°F

, being considerably hotter than the return

water from the system.

3. This is accomplished with the

two internal boiler circulators

.

The Bypass circulator (page 2, item

7

) takes hot water from the

boiler supply outlet and blends it with return water. The System

circulator (page 2, item

6

) slows down to aid in raising the return

temperature entering the sections.

4. If the

temperature mixing system

does not work correctly, check

the two circulators to be sure they are flowing water. If the circula-

tors are operating normally but the temperature mixing system

does not maintain water at the enterance to the boiler sections at

140°F, you may need to replace the boiler IBC or water temperature

sensor (page 2, items

1

and

8

).

Inspect limit controls and cutoffs

1. Inspect and test the boiler limit control. Verify operation by turning

control set point below boiler temperature. Boiler should cycle off.

Return dial to original setting.

2. Inspect and test additional limit controls or low water cutoffs

installed on system. Follow the device manufacturer's instructions.

Inspect gauges

1. Boiler pressure/temperature gauge — Inspect gauge and check

whether readings are reasonable. Replace if any signs of leakage from

case or improper readings.

2. System gauges (if installed) — Inspect and check readings of other

gauges in system.

Annual start-up

(continued)

Figure 79

Blower motor

Inspect blower motor

1. See Figure 79. With boiler power

Off

, place a few drops

of Anderol 465 in each of the two oil cups.

Use only

Anderol 465

to lubricate the blower

motor. Do not use universal household oils.
Motor could be damaged, resulting in possible
severe property damage.

Inspect oiled-bearing circulators

1. Both of the circulators installed in the boiler are water-

lubricated. No oiling is required.

2. Check other circulators in the system. Oil any circula-

tors requiring oil, following circulator manufacturer’s
instructions. Over-oiling will damage the circulator.