Troubleshooting, Gv90, Boiler manual – Weil-McLain GV90+ User Manual

Page 79: Symptom common causes possible corrections

Advertising
background image

Part number 550-142-054/0411

79

GV90+

gas

-

fired

water

boiler

— Boiler Manual

Troubleshooting

(continued)

Figure 94

Common causes and possible corrections, part 1

Symptom

Common Causes

Possible Corrections

Rapid cycling — boiler

turns on and off frequently

Thermostat installed where drafts

or heat affect reading

Locate thermostat on inner wall away from

heat sources or cool drafts.

Heat anticipator in thermostat

adjusted incorrectly

Adjust thermostat per manufacturer’s

instructions.

Incorrect limit setting

Set limit according to system needs.

Maximum setting is 200°F. Increase limit

setting to decrease cycling.

Insufficient water flow through

boiler

Check all valves to and from boiler. Return

to proper setting.

Confirm circulator size.

Frequent release of water

through relief valve

Expansion tank sized too small

Call qualified service technician to check

expansion tank operation and size.

Flooded expansion tank

Call qualified service technician to check

expansion tank operation.

Inoperative limit control

Call qualified service technician to replace

limit control.

Need to frequently add

makeup water

Leaks in boiler or piping

Have qualified service technician repair

leaks at once to avoid constant use of

makeup water. Makeup water can cause

mineral deposits which, in turn, can cause

boiler section failure. Do not use petroleum-

base stop-leak compounds.

Black water condition

Oxygen corrosion due to leaks in

boiler and piping

Have qualified service technician repair at

once. Keep pH of water between 7.0 to 8.5.