Annual start-up

Address reported problems

1. Inspect any problems reported by owner and correct before pro-

ceeding.

Inspect boiler area

1. Verify that boiler area is free of any combustible materials, gasoline

and other flammable vapors and liquids.

2. Verify that air intake area is free of any of the contaminants listed

in Figure 36, page 30. If any of these are present in the boiler intake

air vicinity, they must be removed. If they cannot be removed,

reinstall the air and vent lines per this manual.

Inspect boiler interior

1. Remove jacket top and front door to inspect interior of boiler.

2. Vacuum any sediment and components.

Do not use solvents to clean any of the boiler compo-

nents. The components could be damaged, resulting in

unreliable or unsafe operation.

Inspect condensate drain system

1. Inspect the condensate trap hose for

deterioration

.

2. Check for any obstructions in the trap hose by squeezing the

tubing.

3. If there is any doubt the condensate drain system is flowing freely,

remove the clamp and hose from the bottom of the recuperator.

Slide a funnel outlet into the trap hose and pour water through. It

should exit at the termination of the condensate drain line.

Inspect all piping for leaks

Eliminate all system or boiler leaks. Continual

fresh make-up water will reduce boiler life.

Minerals can build up in sections, reducing

heat transfer, overheating heat exchanger, and

causing heat exchanger failure. Leaking water

may also cause severe property damage.

1. Inspect all water and gas piping and verify to be leak

free.

2. Look for signs of leaking lines and correct any problems

found.

3. Check gas line using procedure on page 54.

Inspect gas piping

1. Sniff near floor and around boiler area for any indica-

tion of a

gas leak

.

2. Test gas piping using bubble test,

per page 54, if

there is any indication of a leak.

Inspect the water system

1. Verify all system components are correctly installed and

operational.

2. Check the cold fill pressure for the system. Verify it is

correct (usually around 12 PSIG).

3. Watch the system pressure as the boiler heats up (dur-

ing testing) to ensure pressure doesn’t rise too high.

Excessive pressure rise indicates expansion tank sizing

or performance problem.

4. Inspect automatic air vents and air separators. Remove

air vent caps and briefly press push valve to flush vent.

Reinstall caps. Make sure vents do not leak. Replace any

leaking vents.

Check water system chemistry

1. Check system water chemistry (pH and hardness). See

instructions beginning on page 59.

2. Check glycol and glycol inhibitor levels if using glycol/

water mixture. See instructions beginning on page 59.

3. Check Sentinel X100 inhibitor level in the water using

the Sentinel X100 Inhibitor Test Kit. Follow instructions

supplied with the kit. Add X100 inhibitor if needed to

bring to the correct level. (See Figure 96, page 89 for

part numbers.)

Do not use petroleum-based cleaning or

sealing compounds in boiler system

. Se-

vere damage to boiler will occur, resulting in

substantial property damage.

Annual start-up only by qualified

service technician

The boiler should be inspected and started annu-

ally, at the beginning of the heating season, only

by a qualified service technician. In addition, the

maintenance and care of the boiler designated in

Figure 77, page 67 and explained on the follow-

ing pages must be performed to assure maximum

boiler efficiency and reliability. Failure to service

and maintain the boiler and system could result

in equipment failure.

Electrical shock hazard — Turn off power to

the boiler before any service operation on the

boiler except as noted otherwise in this instruction

manual. Failure to turn off electrical power could

result in electrical shock, causing severe personal

injury or death.