Gas piping, Gv90, Boiler manual – Weil-McLain GV90+ User Manual

Page 55: Natural gas, Propane gas

Advertising
background image

Part number 550-142-054/0411

55

GV90+

gas

-

fired

water

boiler

— Boiler Manual

Figure 65

Pipe capacity for 0.60 specific gravity natural gas

Gas pipe

length

(feet)

Capacity in cubic feet of gas per hour

Natural gas only, with specific gravity of 0.60

Based on pressure drop of 0.3” w.c.

Gas pipe diameter —

½”

¾”

1”

1¼”

1½”

10

132

278

520

1050

1600

20

92

190

350

730

1100

30

73

152

285

590

860

40

63

130

245

500

760

50

56

115

215

440

670

75

45

93

175

360

545

100

38

79

150

305

460

150

31

64

120

250

380

For additional gas pipe sizing information, refer to ANSI Z223.1 (or

B149.1 orB149.2 for Canadian installations).

Gas piping

(continued)

Natural Gas

1. Refer to Figure 65 for pipe length and diameter.

Size gas supply piping for total flow to all connected

appliances. For each GV90+ boiler, provide for the

following gas flow (cfh = cubic feet per hour):

Boiler model

CFH natural gas

GV90+3

70

GV90+4

140

GV90+5

105

GV90+6

175

2. Inlet pressure required at gas valve inlet:

• maximum 13” w.c.
• minimum 4” w.c.

Install 100% lockup gas pressure regula-

tor in supply line if inlet pressure exceeds

13” water column. Adjust for 13” w.c.

maximum.

Propane Gas

1. Contact gas supplier to size pipes, tanks and 100%

lockup gas pressure regulator.

2. Adjust propane supply regulator provided by gas

supplier for 13” w.c. maximum pressure.

3. Inlet pressure required at gas valve inlet:

• maximum 13” w.c.
• minimum 4” w.c.