Install water piping, Gv90, Boiler manual – Weil-McLain GV90+ User Manual

Page 22

Advertising
background image

Part number 550-142-054/0411

GV90+

gas

-

fired

water

boiler

— Boiler Manual

22

Figure 27

Installing GV90+ boiler in system with

water chiller

Water chiller systems

Pipe the boiler and water chiller as shown in Figure 27.
Install boiler, as shown, so chilled medium is piped in parallel with

heating boiler.
Use appropriate valves to prevent chilled medium from entering boiler.

See Figure 27 for typical installation of balancing valve and check valve.
Install the flow/check valve in the boiler supply piping, as shown in

Figure 27, to prevent gravity circulation during the cooling cycle.
If boiler is connected to heating coils located in air handling units where

they can be exposed to refrigerated air, use flow control valves or other

automatic means to prevent gravity circulation during cooling cycle.

Balancing, when required

Substitute a memory-stop

valve for one of the isolation valves in each zone to use

the memory-stop valve for balancing flow as well as

isolation.

Zoning with zone valves

Provide a separate 24-volt

transformer to power the zone valves. Size the trans-

former to handle the total rated load of all connected zone

valves. Alternatively, use a zone valve zone controller.

Zoning with circulators

— The GV90+ internal system

circulator cannot be removed from the boiler for use as

one of the zone circulators. It must remain as shipped

from the factory to allow proper flow control inside the

boiler. You will need a circulator for each zone. Provide
circulator relays or circulator zone controller.

Chilled water systems often use closed-type expansion

tanks, as shown in Figure 27. DO NOT install automatic

air vents on these systems.

MINIMUM

Boiler loop pipe size

GV90+3/4
GV90+5/6

1”

1¼”

Install water piping

(continued)

Legend

1 Isolation valves

2 Air separator

3 Expansion tank with tank fitting (piping shown for

application of a closed-type expansion tank)

5 System circulator

6 Flow/check valve

8 Boiler pressure/temperature gauge

16 Cold water fill line — see Figure 15, page 14 for typical

components

17 Balancing valve

19 Chiller

20 Strainer

21 Check valve

22 System supply

23 System return

Advertising