Install water piping, Gv90, Boiler manual – Weil-McLain GV90+ User Manual

Page 12

Advertising
background image

Part number 550-142-054/0411

GV90+

gas

-

fired

water

boiler

— Boiler Manual

12

Install water piping

Air separator

Install an

air separator

in the piping as shown in this

manual. For single-zone systems, install the air separator

in the return piping as shown in Figure 14, page 14. This

allows mounting the automatic air vent and expansion tank

off of the separator.

Install relief valve

1. Install relief valve ONLY as shown in Figure 12.
2. Connect discharge piping to safe disposal location, fol-

lowing guidelines in Figure 13, page 13.

Figure 12

Install and pipe relief valve

Legend

1 Jacket plug for unused relief valve jacket open-

ing.

2 Jackets are provided with two relief valve open-

ings because each jacket size is used for two boiler

sizes. Cover the unused opening with the plug

provided.

3 Boiler relief valve (from accessory bag)
4 ¾” x 3” nipple, provided in accessory bag
5 ¾” relief valve tapping in back section
6 Connect minimum ¾” discharge piping to relief

valve.

See Figure 13, page 13.

Use two wrenches when tightening water piping at

boiler

, using one of the wrenches to prevent the boiler

interior piping from turning. Failure to support the boiler

piping connections to prevent them from turning could

cause damage to boiler components.

The cast iron heat exchanger return temperature must

be kept at or above 140°F during all times of operation

to prevent possibility of corrosion due to condensation.

This is done automatically, using the boiler's internal

circulators. DO NOT remove or tamper with these cir-

culators. Failure to comply could result in severe personal

injury, death or substantial property damage.

General piping information

Minimum pipe size for boiler loop piping

Figure 11

Provide boiler loop piping no smaller than listed

below (based on 20°F temperature rise)

Boiler loop pipe size, Minimum

GV90+3 or 4

1”

GV90+5 or 6

1¼”

Additional limit controls

Following standard industry practices, if installation is to comply with

ASME or Canadian requirements, an additional

high temperature

limit

may be needed. Consult local requirements for other codes/

standards to determine if needed. Wire as shown in Figure 67, page 56.
• Install a manual reset high temperature limit between the boiler

and the isolation valve.

• Wire the manual reset limit in series with the boiler limit con-

trol.

• Set the manual reset limit control at least 20°F above the boiler

limit control setting (maximum setting 220°F).

Low water cut-off, when required

A

low water cutoff device

is required when boiler is installed above

radiation level or by certain state or local codes or insurance companies.

Use low water cutoff designed for water installations. Electrode probe-

type is recommended. Purchase and install in tee in supply piping above

boiler. Wire contact as shown in Figure 67, page 56.

If boiler is connected to heating coils located in air han-

dling units where they can be exposed to refrigerated

air, use flow control valves or other automatic means to

prevent gravity circulation during cooling cycle. Circu-

lation of cold water through the boiler could result in

damage to the heat exchanger, causing possible severe

personal injury, death or substantial property damage.

Backflow preventer

Where required by codes, install a

backflow preventer

in the cold

water fill line, as shown in suggested piping diagrams on following

pages. Install a check valve if a backflow preventer is not installed.

Advertising