119

Chapter 6

Response message format for function code 01:

Example: Coils number 2 and 7 are on, all others are off.
01 01 01 42
In the response the status of coils 1 to 8 is shown as the byte value 42 hex,
equal to 0100 0010 binary.

Function Code 02
The function code 02 is used to read the discrete inputs ON/OFF status of
ADAM-6000 in a binary data format.
Request message format for function code 02:

Example: Read coil number 1 to 8 (address number 00001 to 00008) from
ADAM-6000 modules
01 02 00 01 00 08
Response message format for function code 02:

Example: input number 2 and 3 are on, all others are off.
01 02 01 60
In the response the status of input 1 to 8 is shown as the byte value 60
hex, equal to 0110 0000 binary.

Command Body

Station

Address

Function

Code

Byte Count

Data

Data

Command Body

Station

Address

Function

Code

Start

Address

High Byte

Start

Address

Low Byte

Requested

Number of Input

High Byte

Requested

Number of

Input Low Byte

Command Body

Station

Address

Function

Code

Byte Count

Data

Data