Figure 3.4: secure module to a din-rail, 3 wiring & connections, 1 power supply wiring – B&B Electronics ADAM-6066 - Manual User Manual

Page 28: Figure 3.4:secure module to a din-rail, Wiring & connections, Power supply wiring

Advertising
background image

ADAM-6000 Series User Manual

18

Figure 3.4: Secure Module to a DIN-rail

3.3 Wiring & Connections

This section provides basic information on wiring the power supply, I/O
units, and network connection.

3.3.1 Power Supply Wiring

Although the ADAM-6000/TCP systems are designed for a standard
industrial unregulated 24 VDC power supply, they accept any power unit
that supplies within the range of +10 to +30 VDC. The power supply rip-
ple must be limited to 200 mV peak-to-peak, and the immediate ripple
voltage should be maintained between +10 and +30 VDC. Screw termi-
nals +Vs and GND are for power supply wiring.

Note: The wires used should be at least 2 mm.