ADAM-6000 Series User Manual

192

Figure 7.11: Remote Message Output

Note: The total message sent out will include Device Description, the
logic rule number which sends this message, the message index, module
IP, module name and all I/O status.

Local Internal Counter Setting (Counter)
Below are the steps to configure internal counter setting:
1.

Define what action (increase one count to internal counter value by
Positive edge trigger (F->T), or reset internal counter by Reset)
will be taken for the true action (When the logic result value passed
from Execution stage is logic True) by the True Action combo
box.

Note: When you choose Positive edge trigger (F->T) as action, the coun-
ter will only add one count for the first time that the logic result value
from Execution Stage is logic high. After the first time, the counter value
will not change even the logic result value from Execution Stage is still
logic high. So it is the reason why it is called positive edge trigger.