B&B Electronics ADAM-6066 - Manual User Manual

Page 158

Advertising
background image

ADAM-6000 Series User Manual

148

$aaCjCh
Name

Clear Latch Alarm

Description Sets the High/Low alarm to OFF (no alarm) for the specified

input channel in the addressed ADAM-6000 module

Syntax $aaCjCh(cr)

$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
slave network address of an ADAM-6000 module.
(Always 01)
Cj identifies the desired channel j (j : 0 to 7).
Ch is the Clear Latch Alarm command.
h indicates alarm type (H = High alarm, L = Low alarm)
(cr) represents terminating character, carriage return (0Dh)

Response !aa(cr) if the command was valid

?aa(cr) if an invalid operation was entered.
There is no response if the system detects a syntax error or
communication error or if the address does not exist.
! delimiter indicating a valid command was received.
aa represents the 2-character hexadecimal slave address
of the corresponding ADAM-6000 module.
(cr) represents terminating character, carriage return (0Dh)

Example

command: $01C1CL(cr)
response: !01(cr) Channel 1 of the ADAM-6000 module at
address 01h is instructed to set its Low alarm state to OFF.
The system confirms it has done so accordingly.