ADAM-6000 Series User Manual

190

Pulse Output (DO_Pulse)
Below are the steps to configure pulse output:
1.

Choose correct model name by the Target module combo box in the
Operation area.

2.

Define what action (continuous generate pulse train by Continue, stop
pulse generation by Stop, or only generate finite number of pulse by
Num of pulse
) will be taken for the true action (When the logic result
value passed from Execution stage is logic True) from the True
Action
combo box.

3.

The false action (When the logic result value passed from Execution
stage is logic False) is displayed by the False Action text box and will
always be Keep current status, meaning there is no action change for
the selected digital output channel.

4.

Define which digital output channel is responsible to take the defined
action (start or stop pulse generation) by the Channel combo box.

5.

If you choose Num of pulse in the True Action combo box, type the
number of pulse you want to generate in the Value text box.

6.

Click the OK button to complete the configuration.

Local Timer (Timer)
There are 16 local timers on ADAM-6000 module. Here, you can define the
timer action depending on the logic result value from the Execution stage.
After you have chosen Timer in the Operation type combo box, select the
interested timer by the Index combo box in the Operation area. (From timer
0 to timer 15) Then you can define the timer action by the Type combo box
in the Operation area.

When you choose ON-Delay, the timer will start to count the time passed
when the logic result value passed from the Execution stage is logic True,
while the timer will stop counting and reset its value to zero when the logic
result value is logic False. If you choose OFF-Delay, the true action and
false action will be opposite: the timer will start to count the time passed
when the logic result value is logic False, while it will stop counting and rest
its value to zero when the logic result value is logic True. The action
description is displayed by the True/False act text box. After you have com-
pleted the setting, click the OK button.