4 analog input alarm command set set, Analog input alarm command set set – B&B Electronics ADAM-6066 - Manual User Manual

Page 154

Advertising
background image

ADAM-6000 Series User Manual

144

Example command: $01B07(cr)
response: !0112

Since the ADAM-6018 is used, we can know the range code of
channel 7 is 12, meaning “Thermocouple R (500~1750° C)”.

6.4.4 Analog Input Alarm Command Set Set

(ADAM-6015, 6017, 6018)

$aaCjAhs
Name

Set Alarm Mode

Description Sets the High/Low alarm of the specified input channel in

the addressed ADAM-6000 module to either Latching or
Momentary mode.

Syntax $aaCjAhs(cr)

$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
slave network address of an ADAM-6000 module.
(Always 01)
Cj identifies the desired channel j (j : 0 to 7).

Command
Syntax

Command
Name

Description

$aaCjAhs

Set Alarm

Mode

Set the High/Low alarm in either Momentary or Latch-

ing mode

$aaCjAh

Read Alarm

Mode

Returns the alarm mode for the specified channels

$aaCjAhEs

Enable/Dis-

able Alarm

Enables/Disables the high/low alarm of the specified

channels

$aaCjCh

Clear Latch

Alarm

Resets a latched alarm

$aaCjAhCCn Set Alarm

Connection

Connects the High/Low alarm of a specified input

channel to interlock with a specified output channel

$aaCjRhC Read Alarm

Connection

Returns the alarm configuration of a specified input

channel

$aaCjAhU

Set Alarm

Limit

Sets the High/Low alarm limit value to a specified

channel

$aaCjRhU

Read Alarm

Limit

Returns the High/Low alarm limit value of the speci-

fied channel

$aaCjS

Read Alarm

Status

Reads whether an alarm occurred in the specified

channel