Chapter 6

$aaCjAhEs
Name

Enable/Disable Alarm

Description Enables/Disables the High/Low alarm of the specified input

channel in the addressed ADAM-6000 module

Syntax $aaCjAhEs(cr)

$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
slave address of an ADAM-6000 module.
(Always 01)
Cj identifies the desired channel j (j : 0 to 7).
AhEs is the Set Alarm Mode command.
h indicates alarm type (H = High alarm, L = Low alarm)
s indicates alarm enable/disable (E = Enable, D = Disable)
(cr) represents terminating character, carriage return (0Dh)

Response !aa(cr) if the command was valid

?aa(cr) if an invalid operation was entered.
There is no response if the system detects a syntax error or
communication error or if the address does not exist.
! delimiter indicating a valid command was received.
aa represents the 2-character hexadecimal slave address of
the corresponding ADAM-6000 module.
(cr) represents terminating character, carriage return (0Dh)

Example

command: $01C1ALEE(cr)
response: !01(cr)
Channel 1 of the ADAM-6000 module at address 01h is
instructed to enable its Low alarm function.
The module confirms that its Low alarm function has been
enabled.

Note:

An analog input module requires a maximum of 2 seconds
after it receives an Enable/Disable Alarm command to let
the setting take effect.