19

Chapter 3

Figure 3.5: ADAM-6000 Module Power Wiring

We advise that the following standard colors (indicated on the modules)
be used for power lines:
+Vs (R) Red
GND (B) Black

3.3.2 I/O Module Wiring

The system uses a plug-in screw terminal block for the interface between
I/O modules and field devices. The following information must be con-
sidered when connecting electrical devices to I/O modules.
1. The terminal block accepts wires from 0.5 mm to 2.5 mm.
2. Always use a continuous length of wire. Do not combine wires.
3. Use the shortest possible wire length.
4. Use wire trays for routing where possible.
5. Avoid running wires near high-energy wiring.
6. Avoid running input wiring in close proximity to output wiring.
7. Avoid creating sharp bends in the wires.