ADAM-6000 Series User Manual

46

Relay Output
• Channels: 6 (Form A)
• Contact rating (Resistive):AC: 120 V @ 0.5 A

DC: 30 V @ 1 A

• Breakdown voltage: 500 VAC (50/60 Hz)
• Relay on time: 7 millisecond
• Relay off time: 3 millisecond
• Total switching time: 10 milliseconds

• Insulation Resistance: 1 G

minimum at 500 VDC

• Maximum Switching Rate: 20 operations/minute (at rated load)
• Electrical Endurance

At 12 V / 10 mA Typical 5 x 10

7

operations

At 6 V / 100 mA Typical 1 x 10

7

operations

At 60 V / 500 mA Typical 5 x 10

5

operations

At 30 V / 1000 mA Typical 1 x 10

6

operations

At 30 V / 2000 mA Typical 2 x 10

5

operations

• Mechanical endurance Typical 10

8

operations

• Supports pulse output (maximum 3 Hz)

General:
• Built-in Watchdog Timer
• Isolation Protection: 2000 VDC
• Power Input: Unregulated 10 ~ 30 VDC
• Power Consumption: 2 W @ 24 VDC
• Power Reversal Protection
• Operating Humidity: 20 ~ 95 % RH (non-condensing)
• Storage Humidity: 0 ~ 95 % RH (non-condensing)
• Operating Temperature: -10 ~ 70° C
• Storage Temperature: -20 ~ 80° C