ADAM-6000 Series User Manual

246

Remarks:
1.

How to retrieve the counter/frequency value:
Counter (decimal) = (value of 40002) x 65535 + (value of 40001)
Frequency (decimal) = (value of 40001)/10 Hz

2.

Time Unit: 0.1 ms

3.

If the count number is overflow, this bit will be 1. Once this bit is
read, the value will return to 0.

4.

When DI channel is configured as “High to low latch” or “Low to
high latch”, this bit will be 1 if the latch condition occurs. After

Address

0X

Ch Description Attribute Address 4X

Ch

Description

Attribute

00041

2

Counter

Start(1)/

Stop(0)

R/W

40039~40040 1

Set Absolute Pulse

5

R/W

00042

Clear Coun-

ter(1)

Write 40041~40042

2

R/W

00043

Clear
Overflow

3

R/W

40043~40044 3

R/W

00044

DI Latch
Status

4

R/W

40045~40046 4

R/W

00045

3

Counter

Start(1)/

Stop(0)

R/W

40047~40048 5

R/W

00046

Clear Coun-

ter(1)

Write

00047

Clear
Overflow

3

R/W

40049~40050 0

Set

Incremental

Pulse

6

R/W

00048

DI Latch
Status

4

R/W

40051~40052 1

R/W

00049 4 Counter

Start(1)/

Stop(0)

R/W

40053~40054 2

R/W

00050 Clear

Coun-

ter(1)

Write 40055~40056

3

R/W

00051 Clear

Overflow

3

R/W 40057~40058

4

R/W

00052 DI

Latch

Status

4

R/W

40059~40060 5

R/W

00053 5 Counter

Start(1)/

Stop(0)

R/W

00054 Clear

Coun-

ter(1)

Write 40301

All

DI

Value

Read

00055 Clear

Overflow

3

R/W 40303

All

DO

Value

R/W

00056 DI

Latch

Status

4

R/W

40305

0~15 GCL Internal Flag

Value

7

R/W