B.2 adam-6000 i/o modbus mapping table, B.2.1 adam-6015, Adam-6000 i/o modbus mapping table – B&B Electronics ADAM-6066 - Manual User Manual

Page 240: Ch rtd input module

Advertising
background image

ADAM-6000 Series User Manual

230

B.2 ADAM-6000 I/O Modbus Mapping Table

B.2.1 ADAM-6015

7-ch RTD Input Module

Address

0X

Channel Description

Attribute Address 4X Channel Descrip-

tion

Attribute

00101 0

Reset

Historical

Max. Value

R/W 40001

0

AI

Value

Read

00102 1

Reset

Historical

Max. Value

R/W

40002

1 AI

Value

Read

00103 2

Reset

Historical

Max. Value

R/W

40003

2 AI

Value

Read

00104 3

Reset

Historical

Max. Value

R/W

40004

3 AI

Value

Read

00105 4

Reset

Historical

Max. Value

R/W

40005

4 AI

Value

Read

00106 5

Reset

Historical

Max. Value

R/W

40006

5 AI

Value

Read

00107 6

Reset

Historical

Max. Value

R/W

40007

6 AI

Value

Read

00108 -

Reserved

-

40008

-

Reserved -

00109 Average

Ch 0~6

Reset Historical

Max. Value

R/W

40009

Average

Ch 0 ~ 6

AI Value Read

00111 0

Reset

Historical

Min. Value

R/W 40011

0

Historical

Max. AI

Value

Read

00112 1

Reset

Historical

Min. Value

R/W 40012

1

Historical

Max. AI

Value

Read

00113 2

Reset

Historical

Min. Value

R/W 40013

2

Historical

Max. AI

Value

Read

00114 3

Reset

Historical

Min. Value

R/W 40014

3

Historical

Max. AI

Value

Read

00115 4

Reset

Historical

Min. Value

R/W 40015

4

Historical

Max. AI

Value

Read

00116 5

Reset

Historical

Min. Value

R/W 40016

5

Historical

Max. AI

Value

Read

00117 6

Reset

Historical

Min. Value

R/W 40017

6

Historical

Max. AI

Value

Read

00118 -

Reserved

-

40018

-

Reserved -

00119 Average

Ch 0 ~ 6

Reset Historical

Min. Value

R/W

40019

Average

Ch 0 ~ 6

Historical

Max. AI

Value

Read

00121 0

Burnout Flag

1

Read 40021

0

Historical

Min. AI

Value

Read

00122 1

Burnout Flag

1

Read 40022

1

Historical

Min. AI

Value

Read

Advertising