Assigning Addresses in ADAM-6060 Modules
Basied on Modbus/TCP standard, the addresses of the I/O channels in
ADAM-6000 modules are defined by a simple rule. Refer to Appendix
B.2.8 to map the I/O address. All digital input channels in ADAM-6060
are allowed to use as 32-bit counters (Each counter is consisted of two
addresses, Low word and High word). Users could configure the specific
DI channels to be counters via Windows Utility. (Refer to Section 5.3)

4.2.5 ADAM-6066

6-ch Digital Input and 6-ch Power Relay Module
ADAM-6066 is a high-density I/O module with a 10/100 base-T interface
for seamless Ethernet connectivity. ADAM-6066 offers 6 high voltage
power relay (form A) output and 6 digital input channels. It supports con-
tact rating as AC 250V@5A, and DC 30V@3A. All of the digital input
channels support input latch function for signal handling. Meanwhile,
these DI channels can be used as 3 KHz counter and frequency input
channels. Opposite to the intelligent DI functions, the digital output chan-
nels also support pulse output function.

ADAM-6066 Specifications:
• Communication: 10/100 Base-T Ethernet
• Supports Protocol: Modbus/TCP, TCP/IP, UDP, HTTP, ICMP and ARP
• Supports Peer-to-Peer and GCL (Refer to Section 5.3.4 and Chapter 7)

Digital Input
• Channels: 6
• Dry Contact:

Logic level 0: Close to Ground
Logic level 1: Open

• Wet Contact:

Logic level 0: 0 ~ 3 VDC
Logic level 1: 10 ~ 30 VDC

• Supports 3 kHz counter input (32-bit + 1-bit)
• Supports 3 kHz frequency input
• Supports inverted DI status