B&B Electronics ADAM-6066 - Manual User Manual

Page 235

Advertising
background image

225

Appendix B

Response message format for function code 01:

Example: Coils number 2 and 7 are on, all others are off.
01 01 01 42
In the response the status of coils 1 to 8 is shown as the byte value
42 hex, equal to 0100 0010 binary.

Function Code 02
The function code 02 is used to read the discrete input’s ON/OFF status
of ADAM-6000 in a binary data format.
Request message format for function code 02:

Example: Read coil number 1 to 8 (address number 00001 to 00008) from
ADAM-6000 modules
01 02 00 01 00 08

Response message format for function code 02:

Example: input number 2 and 3 are on, all others are off.
01 02 01 60
In the response the status of input 1 to 8 is shown as the byte value
60 hex, equal to 0110 0000 binary.

Command Body

Station

Address

Function

Code

Byte

Count

Data

Data

Command Body

Station

Address

Function

Code

Start Address

High Byte

Start Address

Low Byte

Requested Number

of Input High Byte

Requested Number

of Input Low Byte

Command Body

Station

Address

Function

Code

Byte

Count

Data

Data

Advertising