ADAM-6000 Series User Manual

150

$aaCjRhC
Name

Read Alarm Connection

Description Returns the High/Low alarm limit output connection of a

specified input channel in the addressed module

Syntax $aaCjRhC(cr)

$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
slave address of an ADAM-6000 module. (Always 01)
Cj identifies the desired analog input channel j (j : 0 to 7).
RhC is the Read Alarm Connection command.
h indicates alarm type (H = High alarm, L = Low alarm)
(cr) represents terminating character, carriage return (0Dh)

Response !aaCn(cr) if the command was valid

?aa(cr) if an invalid operation was entered.
There is no response if the system detects a syntax error or
communication error or if the address does not exist.
! delimiter indicating a valid command was received.
aa represents the 2-character hexadecimal slave
address of the corresponding ADAM-6000 module.
Cn identifies the desired digital output channel n (n : 0 to 1)
whether interlock with the alarm of the specific analog input
channel. If the values of n are “*”, the analog input has no
connection with a digital output point.
(cr) represents terminating character, carriage return (0Dh)

Example

command: $01C1RLC(cr)
response: !01C0(cr) Channel 1 of the ADAM-6000 module
at address 01h is instructed to read its Low alarm output
connection.
The system responds that the Low alarm output connects to
the digital output at channel 0 in the specific module.