Figure 7.18: configuration of logic rule 2, Figure 7.19: configuration of logic rule 3 – B&B Electronics ADAM-6066 - Manual User Manual

Page 209

Advertising
background image

199

Chapter 7

Figure 7.18: Configuration of Logic Rule 2

Figure 7.19: Configuration of Logic Rule 3

Using Local or Distributed Logic Cascade architecture, there will be no
limitation for input numbers of logic rules. And you can build any logic
architecture to meet your application requirement.

Mode: Analog

Channel: 1

Condition: >=

Value: 3.00

Mode: Analog

Channel: 1

Condition: <=

Value: 5.00

Logic Rule 2 on Module B (IP: 196.168.3.20)

Destination:

196.168.3.30 (IP of Module C)

Operation Type: AuxFlag

True Action: True

Index: 1

Mode: AuxFlag

Index: 0

Condition: True

Mode: AuxFlag

Index: 1

Condition: True

Destination: Local

Operation Type: DO

True Action: True

Channel: 0

Logic Rule 3 on Module B (IP: 196.168.3.30)