209

Chapter 7

We need to use 1 Internal Flag (Flag 0) and 2 logic rules for the Flicker
application described above. In logic rule 1, the value of Flag 0 is
inverted (By choosing NAND in the Logic stage) periodically. (Here, it is
0.5 second) The period is defined by the Execution_Period in the Execu-
tion
Stage. (Refer to the Section 7.3.3) The status of DO 0 is controlled
by Flag 0 in logic rule 2, so DO 0 will change every 0.5 second. The GCL
logic rule architecture is shown by Figure 7.30 below:

Figure 7.30: GCL Logic for Flicker

6.

Rising Edge

For Rising Edge application, the DO status will be activated to logic high,
when DI value is changed from logic low to logic high (it is so-called ris-
ing edge). But the DO value won’t continuously remain logic high.
Instead, after a specific time interval (in the example, it is 1 second), the
DO value will return to logic low. Refer below for its time chart:

Figure 7.31: Time Chart for Rising Edge

AND

Flag 0

DO 0

AND

Flag 0

Rule 1

Rule 2

Period

500 ms

Inverse

Flag 0

Period

0 ms

DO 0

Time

T0

T1

T0 + 1 second

T1 + 1 second

DI 0

Rising Edge