Figure 4.17: adam-6052 di (dry contact) wiring, Figure 4.17:adam-6052 di (dry contact) wiring – B&B Electronics ADAM-6066 - Manual User Manual

Page 53

Advertising
background image

43

Chapter 4

Digital Output
• Channels: 8
• Source Type: 10 ~ 35 VDC, 1 A (per channel)
• Supports 5 kHz pulse output
• Supports high-to-low and low-to-high delay output

General:
• Built-in Watchdog Timer
• Isolation Protection: 2000 VDC
• Power Input: Unregulated 10 ~ 30 VDC
• Power Consumption: 2 W @ 24 VDC
• Power Reversal Protection
• Operating Humidity: 20 ~ 95 % RH (non-condensing)
• Storage Humidity: 0 ~ 95 % RH (non-condensing)
• Operating Temperature: -10 ~ 70° C
• Storage Temperature: -20 ~ 80° C

Application Wiring

Figure 4.17: ADAM-6052 DI (Dry Contact) Wiring

DI GND

DI 7
DI 6
DI 5
DI 4
DI 3
DI 2
DI 1
DI 0

RJ-45

(Ethernet)

DI_COM
DO_VCC
DO 0
DO 1
DO 2
DO 3
DO 4
DO 5
DO 6
DO 7
DO_GND
(R) +Vs
(B) GND

Dry Contact