B&B Electronics ADAM-6066 - Manual User Manual

Page 239

Advertising
background image

229

Appendix B

Response message format for function code 08:
The normal responses return the station address, function code, start
address, and requested number of coil forced.

Example: 01 0F 00 11 00 0A

Function Code 16 (10 hex)
Preset values into a sequence of holding registers.
Request message format for function code 16:

Example: Preset constant #1 (address 40009) to 100.0 in ADAM-6000
module.

01 10 00 09 00 02 04 42 C8 00 00

Response message format for function code 08:
The normal responses return the station address, function code, start
address, and requested number of registers preset.

Example: 01 10 00 09 00 02

Command Body

Station

Address

Function

Code

Start Address

High Byte

Start Address

Low Byte

Requested Number

of Coil High Byte

Requested Number

of Coil Low Byte

Command Body

Station

Address

Function

Code

Start

Address

High

Byte

Start

Address

Low Byte

Requested

Number

of Register High

Byte

Requested

Number

of Register Low

Byte

Byte

Count

Data

Command Body

Station

Address

Function

Code

Start Address

High Byte

Start Address

Low Byte

Requested Number

of Register High

Byte

Requested Number

of Register Low Byte