B&B Electronics ADAM-6066 - Manual User Manual

Page 59

Advertising
background image

49

Chapter 4

Relay Output
• Channels: 6 (Form A)
• Contact rating (Resistive): AC: 250 V @ 5 A

DC: 30 V @ 3 A

• Breakdown voltage: 500 VAC (50/60 Hz)
• Relay on time: 7 millisecond
• Relay off time: 3 millisecond
• Total switching time: 10 milliseconds

• Insulation Resistance: 1 G

minimum at 500 VDC

• Maximum Switching Rate: 20 operations/minute (at rated load)
• Electrical Endurance

At 30 VDC / 3 A

Typical 1 x 10

5

operations

(Operating frequency 20 operations/minute)

At 250 VAC / 3 A

Typical 1 x 10

5

operations

(Operating frequency 20 operations/minute)

• Mechanical endurance

Typical 2 x 10

7

operations

(Under no load at operating frequency of 180 operations/minute)
• Supports pulse output (maximum 3 Hz)

General:
• Built-in Watchdog Timer
• Isolation Protection: 2000 VDC
• Power Input: Unregulated 10 ~ 30 VDC
• Power Consumption: 2.5 W @ 24 VDC
• Power Reversal Protection
• Operating Humidity: 20 ~ 95 % RH (non-condensing)
• Storage Humidity: 0 ~ 95 % RH (non-condensing)
• Operating Temperature: -10 ~ 70° C
• Storage Temperature: -20 ~ 80° C